AMS 3211-600

The ZrO2 flue gas probe AMS 3211-600 is designed for process applications with temperatures of up to 1750 °C.

To protect the ZrO2 sensor against the influence of the high temperature the sensor is located in the flange of the probe. With an integrated pneumatic pump the process gas is fed to the sensor. This kind of construction guarantees easy service, since the probe does not have to be dismounted to replace the ZrO2 sensor.

Additional product features:

  • immersion depth of 150 mm to 1000 mm
  • probe tubes made of ceramic or Kanthal, depending on process temperature
  • longer life expectancy of the ZrO2 sensor due to the reduced thermal load
  • fast and easy sensor replacement
  • flanges in DIN- or ANSI-sizes available
  • continuous monitoring of sensor signal, -heater and measuring value on plausibility by the Transmitters AMS 3220 or AMS 5200
  • back-purge and auto-calibration features are available as options
AMS 3211-600

Technical data

ZrO2 probe AMS 3211-600
Measuring principle ZrO2 probe with Pt-electrodes
Application Residual oxygen in flue gas
Construction ZrO2 sensor installed in the sensor flange with pneumatic pump
Flue gas temp., max. 1700 °C
Dust content (flue gas) max. 5 grams/Nm3
Flue gas velocity < 20 m/s
Time for pre-heating ~ 10 Minutes
T90-Time < 20 Seconds
Reaction time < 5 Seconds
Probe length 150 – 1000 mm
Connecting flanges DN 80 PN 16, DN 100 PN 16
Material Ceramics, Kanthal
Installation in the stack straight down
Protection IP 65
Reference air supply by separate pneumatic unit
Calibration gas supply by separate pneumatic unit
Weight ca. 6,5 kg
Accessories  
Transmitter AMS 5200 / AMS 3220 in housing IP 65
Pneumatic unit GRP housing, Dimensions: 600 x 600 x 200 mm /
  800 x 600 x 300 mm, optional autocalibration
Version: AMS 3211-600 E V-2013-07